GNT-200 Cooling Tower | ||||
No. | Item | Specification | Remark | |
Total |
1 | Capacity Required | 3543.75kw | |
2 | Fluid | Water | ||
3 | Water Inlet | 55ºC | ||
4 | Water Outlet | 30ºC | ||
5 | Wet Bulb Temperature | 20ºC | ||
6 | Overall Dimension(L*W*H)mm | 8,640 x 2,160 x 2,600 mm | ||
7 | Maximum Installed Power | 8.8kw | ||
Fan |
8 | Fan Type | Axial-flow | |
9 | Fan Qty. (set) | 4 | ||
10 | Air Volume of Single Fan (m³/h) | 32,300 | ||
11 |
Motor Brand | Siemens | ||
Each Motor Rated Power (Kw) | 2.2KW |
12 | Material of Fan Blade | Top Quality FRP | ||
13 | Protection & Insulation Level | IP55 & Class F | ||
Casing |
14 |
Material of Casing | Top Quality FRP | |
Material of Water Basin | Top Quality FRP | |||
15 |
Advantages |
Over 18 years Long life Span, Anti-aging, Anti-Ultraviolet, Fastness |
||
Base& Bracket |
16 | Material of Bracket Support | #304 Stainless Steel | |
17 | Bottom Base Frame | HDG Steel | ||
Infill & Drift Eliminator |
18 | Infill | "S" type | |
19 | Material | PVC (Imported Top Quality) | ||
20 | Water Drift Rate | ≤0.005% | ||
Water Distribution System |
21 | Water Distribution Type | Tube Type | |
22 | Nozzle | ABS | ||
23 |
Struture Advantages |
Even water distribution, Water distribution range 70% to 130% of rated water flow rate, Anti-block performance |
||
Inlet/Outlet | 24 | Water Inlet | DN80 x 4 | Four water inlet |
Standard | 25 | Design Standards | CE Standards |